A restaurant’s rooftop unit. With the access panel off, the evaporator coil was iced across its face, and the filter section next to it was frosted too.

An air conditioner ices for two broad reasons: not enough air over the coil, or not enough refrigerant in it. Either way the coil runs below freezing, the water on it freezes instead of draining, and the ice blocks more air, which makes the coil colder, which makes more ice. Once it’s like this you can’t test anything. It has to thaw first.

The filters are 20x25x2 pleats.

Down in the compressor section, there was frost on both suction lines and on the bottom of both compressors. That’s liquid refrigerant making it back toward the compressors because the iced coil can’t boil it all off, and it’s hard on a compressor.

We went back a few days later with thermometers, and that visit is its own post. If your rooftop unit is iced, leave it off and call.