A prep table in a restaurant kitchen stopped cooling. Its condensing unit sits in the basement, and the compressor wasn’t running.

This is the compressor’s terminal block. The spade connectors on the run and start terminals had cooked. Insulation burnt back, copper blackened, one terminal barely making contact.

It’s a slow failure. A connector loosens a little, resistance goes up, that spot heats, the heat oxidises the metal, resistance goes up again. Months later there’s enough heat to melt the insulation, and the compressor either can’t start or trips its overload. From the kitchen it looks like a dead compressor. It isn’t.

The fix: a new terminal harness with proper insulated connectors, then a check of the start relay, the overload, the run capacitor and the delay-on-make timer in the control box. Then running amps measured against the plate to make sure the compressor itself was healthy. It was.

Compressors are the expensive part. Before anyone quotes you one, the connections at the terminals should be looked at with the cover off. A burnt harness is a small repair. A compressor swap on a prep table is often more than the prep table is worth.